This is the authors' abstract. We don't add key points for this paper.
With the integration of wind power into power systems continues to increase, the impact of high penetration of wind power on power system stability becomes a very important issue. This paper investigates the impact of doubly fed induction generator (DFIG) control and operation on rotor angle stability. Acontrol strategy for both the rotor-side converter (RSC) and grid-side converter (GSC) of the DFIG is proposed to mitigate DFIGs impacts on the system stability. DFIG-GSC is utilized to be controlled as static synchronous compensator (STATCOM) to provide reactive power support during grid faults. In addition, a power system stabilizer (PSS) is implemented in the reactive power control loop of DFIG-RSC. The proposed approaches are validated on a realistic Western System Coordinating Council (WSCC) power system under both small and large disturbances. The simulation results show the effectiveness and robustness of both DFIG-GSC control strategy and PSS to enhance rotor angle stability of power system.
No takes yet. Share an insight, caveat, or question.
Edrah et al. (2015) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: