This paper presents a new control approach for enhancing the fault ridethrough capability of wind farms connected to the grid through a voltage-source-converter-based high-voltage dc transmission line. A controlled voltage drop in the wind farm collector grid is initiated upon the occurrence of fault in the high-voltage grid in order to achieve fast power reduction. In the process, a dc voltage of defined magnitude and duration is injected by the sending-end converter together with the voltage reduction to suppress the dc component of the short-circuit current arising from the voltage reduction. As a result, the electrical and mechanical stress on the wind turbines, especially on the DFIG-based units and their converters, are mitigated. Using a test network, the improvement in the fault ridethrough capability of the system that can be achieved by employing the proposed method has been demonstrated.
No takes yet. Share an insight, caveat, or question.
Erlich et al. (2014) studied this question.