A method to synchronize and control a system of parallel single-phase inverters without communication is presented. Inspired by the phenomenon of synchronization in networks of coupled oscillators, we propose that each inverter be controlled to emulate the dynamics of a nonlinear dead-zone oscillator. As a consequence of the electrical coupling between inverters, they synchronize and share the load in proportion to their ratings. We outline a sufficient condition for global asymptotic synchronization and formulate a methodology for controller design such that the inverter terminal voltages oscillate at the desired frequency, and the load voltage is maintained within prescribed bounds. We also introduce a technique to facilitate the seamless addition of inverters controlled with the proposed approach into an energized system. Experimental results for a system of three inverters demonstrate power sharing in proportion to power ratings for both linear and nonlinear loads.
No takes yet. Share an insight, caveat, or question.
Johnson et al. (2014) studied this question.