This paper presents the development and test of a flexible control strategy for an 11-kW wind turbine with a back-to-back power converter capable of working in both stand-alone and grid-connection mode. The stand-alone control is featured with a complex output voltage controller capable of handling nonlinear load and excess or deficit of generated power. Grid-connection mode with current control is also enabled for the case of isolated local grid involving other dispersed power generators such as other wind turbines or diesel generators. A novel automatic mode switch method based on a phase-locked loop controller is developed in order to detect the grid failure or recovery and switch the operation mode accordingly. A flexible digital signal processor (DSP) system that allows user-friendly code development and online tuning is used to implement and test the different control strategies. The back-to-back power conversion configuration is chosen where the generator converter uses a built-in standard flux vector control to control the speed of the turbine shaft while the grid-side converter uses a standard pulse-width modulation active rectifier control strategy implemented in a DSP controller. The design of the longitudinal conversion loss filter and of the involved PI-controllers are described in detail. Test results show the proposed methods works properly.