The use of dissolved hydrogen as an early warning signal of digester failure and a control parameter to operate anaerobic digesters was investigated. A sensitive, on-line method was developed for measuring trace levels of dissolved hydrogen in a semi-permeable membrane, situated within the biomass of a 1 L laboratory anaerobic digester, using trace reduction gas analysis. At normal operating conditions, the dissolved hydrogen partial pressure (2 to 8 Pa) was found to be linearly correlated with the loading rate of the digester, and was a sensitive indicator of the effect of shockloads as well as gradual overloading. An increase in hydrogen partial pressure above a critical concentration of 6.5-7 Pa indicated the initial stage of digester overloading (i.e., volatile fatty acids accumulation). A H(2)-based computer control system, using a critical hydrogen partial pressure of 6.5 Pa as the setpoint, was found to be effective for the safe operation of a laboratory digester close to its maximum sustainable loading rate. The existence of a relationship between hydrogen level and organic loading rate was also confirmed on a 600 m(3) industrial digester, with digester overloading occurring at hydrogen concentrations above 7 Pa. The results suggest that the dissolved hydrogen concentration is capable of being a sensitive on-line parameter for the automated management of anaerobic digesters near their maximum sustainable loading capacity.
No takes yet. Share an insight, caveat, or question.
Cord‐Ruwisch et al. (1997) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: