In this paper, a two-stage approach is introduced to efficiently solve the optimal voltage regulation problem in radial medium-voltage (MV) distribution networks. The proposed method uses the available reactive power of distributed generation units and the on-load tap changer (OLTC) of the high-voltage/MV transformer to regulate network voltages, while also minimizing two conflicting objectives, namely the network energy losses and the frequency of tap changes. This bi-objective optimal voltage regulation problem is addressed in two distinct stages. In the first stage, the network is linearized and a simplified optimal voltage regulation problem is solved to determine the candidate OLTC operating plans (COOPs). For each COOP, a new reactive power allocation method is employed in the second stage to regulate the network voltages and minimize network losses. This method follows a rule-based approach, also allowing its implementation under real-field conditions. The final outcome of this two-stage process is the Pareto-front which can be used by the distribution system operators to select the most preferable solution for the real-time network operation. The proposed methodology is characterized by reduced computational complexity compared to the application of conventional optimization techniques. Time-domain and time-series simulations on a radial MV distribution network are employed to thoroughly evaluate the performance of the proposed method.
No takes yet. Share an insight, caveat, or question.
Kryonidis et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: