Answers are grounded in this paper and cite their sources.
This paper presents a new series capacitor based frequency scan method to assess the subsynchronous resonance risk including induction generator effect (IGE) and subsynchronous control interaction (SSCI). Most existing frequency scan methods are generator based and calculate the impedance as viewed from the neural bus of the study generator. In this paper, the generator-based frequency scan method is discovered to be inadequate or inapplicable to deal with a cluster of inverter-based generation resources under some circumstances. The proposed method scans the impedance as viewed from the series capacitor to assess the IGE/SSCI risk. With nearby inverter-based generation resources modeled by their frequency-dependent impedances, the proposed method is capable of assessing the IGE/SSCI risk for a cluster of inverter-based generation resources. The electromagnetic transient simulation was conducted to validate the proposed method. The proposed method also successfully demonstrates the nonlinear impact of the number of in-service units on the SSCI performance for a cluster of inverter-based generators.
No takes yet. Share an insight, caveat, or question.
Cheng et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: