In this paper, clearing of DC faults in a hybrid multi-terminal HVDC transmission system consisting of line commutated converters (LCCs) and voltage source converters (VSCs) implemented using half-bridge modular multilevel converter (MMC) technology is investigated. While the hybrid HVDC system has several possible configurations, this paper focuses on two of them: 1) a half-bridge MMC-HVDC link piggy-backing on the transmission line of a LCC-HVDC link and 2) LCC-HVDC link tapped by half-bridge MMC inverters. The proposed dc fault recovery strategy employs a high rating series diode valve placed at each VSC inverter pole to block fault currents; AC circuit breakers to isolate the faulty VSC rectifier pole; and force retardation applied at LCC rectifier to extinguish the arc. Detailed simulations demonstrate fast fault recovery performance with the proposed fault recovery procedure. In the case where a single transmission line is shared by the LCC and VSC links, the VSC rectifier is subjected to considerably high current for a period of few hundreds of milliseconds and the ac side voltage dips momentarily. During a single pole fault, interrupting power flow on the healthy pole of VSC rectifier may be necessary to maintain smooth operation.
No takes yet. Share an insight, caveat, or question.
Haleem et al. (2018) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: