Answers are grounded in this paper and cite their sources.
This paper presents voltage stability analysis and improvement of power system when there is increase in wind power penetration. Loading parameter-Voltage curve was used to calculate the loadability and the megawatt margin as the penetration level (PL) of Squirrel Cage Induction Generator Wind System (SCIG-WS) increases. Furthermore, the effects of increasing SCIG-WS PL on grid losses and equipment loading have been investigated. The results show that for the IEEE 14-bus system utilised as case study, the maximum SCIG-WS PL obtainable without reactive power compensation is 49.45%. However, increasing PL has considerable overloading effects on critical transmission lines and generators, which therefore limits the permissible PL to 33.73%. The results also indicate that the application of Static Var System (SVS) yields a significant enhancement in system loadability and reduction in power losses of the system.
No takes yet. Share an insight, caveat, or question.
Adetokun et al. (2020) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: