With the proliferation of distributed generation in distribution networks, quickly and smoothly converting to a state of regional autonomy in the case of distribution network failure is one of the main challenges for the stable operation of a multimicrogrid (MMG). To address the aforementioned problem, this paper proposes coordinated control of the passive transition from grid-connected to islanded operation for a three/single-phase hybrid MMG. Under the premise of fully considering the constraints on the tie-line transfer power undertaken by the master power supply (MPS), the following two scenarios regarding safety and emergency are formulated: 1) when the output power of the MPS is in the safe range, the proposed strategy coordinates the energy storage (ES) in each submicrogrid (SMG) to achieve power balance; 2) when the output power is in the emergency range, this paper proposes a three-phase balance method based on a bubble sort to realize the combination optimization of the single-phase source-load-storage (SLS) and a fast power regulation method based on implicit enumeration for the SLS to reduce the tie-line transfer power, which could prevent failure of the mode transition from power overload. The test results verify the effectiveness and feasibility of the proposed coordination strategy.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2019) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: