The paper presents the design and experimental results of a Thomson coil based fast mechanical switch for hybrid AC and DC circuit breakers rated at 30 kV voltage and 630 A current. The compact design with optimized circuit parameters and geometric dimensions of components targets 2 mm travel within 1 ms when driven by a 2 mF capacitor bank pre-charged to 500 V. The use and design of a disc spring as the damping and holding mechanism is presented. Structural design of a complete switch assembly rather than just the actuator is given. Experimental results show that the switch can travel 1.3 mm in the first 1 ms, and 3.1 mm in the first 2 ms when driven by a 360 V 2 mF capacitor bank. Such fast mechanical switches facilitate hybrid circuit breaker interruptions within 2 or 3 milliseconds for ultra fast and highly efficient protections in 5–35 kV medium voltage DC as well as AC systems.
No takes yet. Share an insight, caveat, or question.
Peng et al. (2015) studied this question.