In this paper the hosting capacity considering voltage unbalance is estimated for single-phase photovoltaic inverters (PVIs) in low-voltage distribution networks in Sweden. A stochastic approach is used to calculate the negative-sequence voltage unbalance for each of the possible locations in the network. The method has been applied to 6 and 28-customer networks for the connection of 6-kW single-phase PVIs. The impact of three-phase motors on the unbalance was also studied. From the results, it was observed that the contribution from single-phase photovoltaic inverters to the voltage unbalance likely exceeds 1%, but unlikely that it will reach 2% of voltage unbalance.