This paper proposes the use of Sprott chaos synchronization (SCS)-based voltage relays for fault protection in microdistribution systems (MDSs). The Sprott chaos system is used as a voltage detector to track the dynamic errors between the normal signal and disturbance signals. The proposed voltage relay is used to detect disturbances, such as serious voltage sag and swell, and uses a critical trigger time to isolate the fault section. It is proposed that the restoration strategy then restores the unfaulted but blackout zones, and confirms security operations, including load-power balance, power generation limits, voltage limits, and power-flow limits. Computer simulations are conducted by using an IEEE 30-bus power system and MDSs, to show the effectiveness of the proposed method.