Accurate assessment of winding condition for power transformers is critical for ensuring the stable operation of modern power systems. Vibration signal has been regarded as an effective and promising evaluator for winding diagnosis. While on-line vibration monitoring offers the continuous, non-invasive and in-service assessment for winding condition, establishing precise correlations between the variable vibration patterns and specific winding condition remains challenging. To this end, an off-line vibration response analysis (VRA) technique was presented in the paper. Specifically, vibration frequency response (VFR) curves, indicating the winding response, were first obtained when the transformer was excited by the developed vibration response testing system, consisting of constant current variable-frequency power supply, intermediate transformer, accelerometers, data acquisition, control and analysis system. The VFR curves were then quantitatively and comprehensively described through four kinds of correlation indices. Finally, hierarchical integration strategy was proposed to aggregate those indices into quantitative criterion for condition assessment. The proposed method was validated on a real transformer under both normal and fault conditions, demonstrating superior performance. Notably, a 10% decrease in the evaluation criterion indicates an incipient winding looseness, while a reduction of 25% or more suggests severe looseness, prompting timely maintenance recommendations.