A practical mitigation of the geomagnetic disturbance (GMD) consequences in power systems is not possible without taking into account the equipment thermal limits and operational constraints. This paper presents such limitations, develops the required equations and characteristics, and proposes a general and comprehensive approach to incorporate these limits in any short-term or long-term geomagnetically induced current (GIC) mitigating solution. As an application, this study formulates the limits in the context of an optimal placement of the GIC blocking devices at the neutral point of the power transformers in the IEEE 118-bus benchmark study system. The proposed optimization problem takes into account synchronous generator real/reactive power capability, acceptable bus voltage magnitudes, transformer hot-spot heating, transmission-line thermal limits, capacitor bank harmonic loading, and synchronous generator rotor heating. This paper shows that the existing standards significantly underestimate the generator rotor heating under the GMD conditions and propose more accurate alternatives. The study results show that considering the equipment thermal limits results in a noticeably different solution when compared with the case of ignoring such limits.