This paper provides a theoretical and experimental discussion about the performance, availability, and flexibility of a battery energy storage system (BESS) using a modular multilevel cascaded converter based on single-star bridge cells (MMCC-SSBC). The SSBC-based BESS produces three-phase multilevel voltage waveforms, and eliminates both harmonic filters and a complicated zig-zag transformer from the ac side. The circuit modularity of the SSBC enables the usage of multiple individual low-voltage battery modules. Along with control strategy based on zero-sequence-voltage injection, this modularity enhances the availability and flexibility of the BESS. A three-phase laboratory downscaled system rated at 140 V, 10 kW, and 21 kW·h is designed, constructed, and tested to verify the operating principles and performance. The tested BESS produces a current total harmonic distortion (THD) of 3.0% even when it operates with different active-power commands for individual bridge cells. In addition, zero-voltage ride-through capability is verified for the severest single-phase, two-phase, and three-phase voltage sags. Mathematical analysis and experimental verification validate the downscaled system and performance, making the BESS prospective.
No takes yet. Share an insight, caveat, or question.
Ota et al. (2015) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: