Answers are grounded in this paper and cite their sources.
Recently the hybrid multi-port DC circuit breaker (MP-DCCB) is becoming popular in protecting HVDC grids, thanks to their reduction of power electronics devices. In this paper, an enhanced multi-port current-limiting DCCB (MP-CLCB) for multiple line protection is proposed. The integrated fault current limiter (FCL) inside the MP-CLCB can clear the fault faster with slightly increased costs. To reduce the energy dissipation requirement for the surge arresters caused by the newly added current-limiting path, an energy transfer path which provides a loop with the inductors during the current decay stage is designed. The theoretical analysis of the pre-charging, current-limiting, fault interruption and energy dissipation of the MP-CLCB is carried out. Moreover, the design principles of the energy dissipation and the key parameters of the MP-CLCB are provided. The proposed approaches are verified through simulations in PSCAD/EMTDC. The results show that the MP-CLCB can replace multiple DCCBs, accelerate the fault current interruption and reduce the energy dissipation requirement for the surge arresters.
No takes yet. Share an insight, caveat, or question.
Xu et al. (2020) studied this question.