In this paper, we consider false data injection (FDI) attacks with limited information of transmission-line susceptances and new countermeasures in smart grids. First, we prove that the adversary could launch FDI attacks to modify the state variable on a bus or superbus only if he/she knows the susceptance of every transmission line that is incident to that bus or superbus. Based on this observation, we provide a new countermeasure against FDI attacks, i.e., to make the susceptances of n-1 interconnected transmission lines that cover all buses unknown to the adversary (e.g., by proactively perturbing transmission-line susceptances through distributed flexible AC transmission system (D-FACTS) devices), where n is the total number of buses. This new countermeasure can work alone or in conjunction with traditional ones to reduce the number of meter measurements/state variables that are to be secured against FDI attacks. The implementation of FDI attacks with limited susceptance information and the effectiveness of new countermeasures are demonstrated by using an illustrative 4-bus power system and the IEEE 9-bus, 14-bus, 30-bus, 118-bus, and 300-bus test power systems.
Deng et al. (Mon,) studied this question.