A rectifier type superconducting fault current limiter with noninductive reactor has been proposed by the authors. The concept behind this SFCL is that the high impedance generated during superconducting to normal state of the trigger coil limits the fault current. In the hybrid bridge circuit of the SFCL, two superconducting coils: a trigger coil and a limiting coil are connected in anti-parallel. Both the coils are magnetically coupled with each other and could have the same value of self inductance so that they can share the line current equally. At fault time when the trigger coil current reaches a certain level, the trigger coil changes from superconducting state to normal state. This super to normal transition of the trigger coil changes the current ratio of the coils and therefore the flux inside the reactor is no longer zero. So, the equivalent impedance of both the coils is increased and limits the fault current. We have carried out computer simulation using PSCAD/EMTDC and observed the results. Both the simulation and preliminary experiment shows good results. The advantage of using hybrid bridge circuit is that the SFCL can also be used as circuit breaker.