Hybrid photovoltaic (PV)-battery-hydropower microgrids (MGs) can be considered to enhance electricity accessibility and availability in remote areas. However, the coexistence of different renewable-energy sources with different inertias and control strategies may affect system stability. In this paper, a hierarchical controller for a hybrid PV-battery-hydropower MG is proposed in order to achieve the parallel operation of the hydropower and PV-battery system with different rates and to guarantee power sharing performance among PV voltage-controlled inverters, while the required power to the hydropower-based local grid is supplied. In this case, the PV-battery system will operate as a PQ bus to inject the desired active and reactive powers to the local grid, while the hydropower station will act as a slack bus which maintains its voltage amplitude and frequency. An integrated small-signal state-space model is derived to analyze the system stability of the hybrid MG. The simulation results show system frequency and voltage stability for a hybrid MG demonstration which includes the 2-MWp PV installations, a 15.2-MWh battery system, and a 12.8-MVA hydropower plant. The experimental results on a small-scale laboratory prototype verify the validity of the theoretical analysis and proposed control strategy.
No takes yet. Share an insight, caveat, or question.
Guan et al. (2015) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: