Legionella pneumophila strains isolated from six patients, three air-conditioning- and cooling tower-derived strains, and three hot water supply-derived strains were analyzed by three genetic typing methods. The results of the whole-cell DNA restriction endonuclease analysis and the restriction patterns based on genes coding for rRNA correlated with each other and demonstrated that the patient isolates were indistinguishable from the air-conditioning- and cooling tower-derived isolates but differed markedly from the hot water supply-derived isolates. The patient and air-conditioning- and cooling tower-derived strains contained plasmids of the same molecular weight; the hot water supply-derived strains were plasmidless. These results indicated that the cooling tower or the air-conditioning system was the environmental source for the examined cluster of Legionnaires disease strains.
No takes yet. Share an insight, caveat, or question.
Ketel et al. (1989) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: