The field performance of an induced trench installation is compared to the results of centrifuge testing and numerical modelling. The measured vertical pressure at the crown of the pipe in the field ranged from 0.24 to 0.36 times the overburden pressure. The horizontal earth pressures measured in the field at the springline level determined a coefficient of lateral earth pressure between 0.39 and 0.49. The culvert was monitored over a period of 2 years following completion of embankment construction indicating no measurable changes in earth pressures and deformations. A model box culvert simulating the prototype height of soil cover, the pipe width, and the thickness of the compressible layer was tested using a geotechnical centrifuge. The prototype structure was also evaluated using numerical modelling to predict full earth pressure distribution and deformations. A comparison of field data, centrifuge testing, and numerical modelling shows that the Marston–Spangler theory used in designing induced trench culverts is conservative. The theory however, does not address or predict the nonuniform pressures on the top, sides, or bottom of the pipe, and therefore numerical analysis should be used to estimate the complete pressure distribution.