Answers are grounded in this paper and cite their sources.
In this paper, we present a new flame monitor that uses three photovoltaic cells covering the ultraviolet (UV), visible, and infrared (IR) spectral bands. A gain-adjustable amplifier is incorporated into the monitor so that it is applicable to the coal-, oil-, or gas-fired flames. Self-checking of the monitor is implemented through cross correlation of the signals from the three cells, and hence, no additional self-checking hardware is required. Both the oscillation frequency and the brightness of the flame are used to monitor flame stability and to detect flame presence as well as sighting-tube blockage. Unlike conventional single-cell flame detectors, the new multicell devices can still be in operation before being repaired, after a cell-failure alarm has gone off. Experiments were carried out on an industrial-scale combustion test facility in order to demonstrate the operability and efficacy of the new flame monitor.
No takes yet. Share an insight, caveat, or question.
Xu et al. (2006) studied this question.