In large plants with high primary fault levels, the whole plant must be considered as forming the ground grid for the return of primary fault current. The internal impedance of the equivalent ground grid must be taken into account in grid potential rise calculations, as grid potentials transferred from one area of the plant may cause hazardous touch potentials at other locations. Field measurements and computer analyses to calculate the distribution of grid potential rise in a large grounding system are presented.
No takes yet. Share an insight, caveat, or question.
Simpson et al. (1987) studied this question.