Designing a reclaimed water system provides an economically and environmentally favorable method for disposing of wastewater. However, some critical influences on on-site reclaimed water systems, such as limited building area, often limit the effectiveness of conventional treatment methods. This work established a compact and inexpensive electrocoagulation process with a capacity of 28m3∕day to reclaim domestic greywater for human noncontact usage. The total unit cost of on-site domestic greywater reuse was U.S.$0.27∕m3, which was below the local potable water rate. Moreover, the treatment facility required an area of 8m2. Both unit cost and required area in this work are lower than those reported in the literature. The experimental results support the feasibility of the on-site reuse of greywater in high-rise buildings.
No takes yet. Share an insight, caveat, or question.
Lin et al. (2005) studied this question.