This paper studies the significant impact of distributed-energy-resource (DER) inverters (which are connected to the same node) on anti-islanding protection of DER-installations. As it concerns the harmonic injection-based schemes, the induced harmonic voltage component that is provoked by each inverter is compromised, as synchronous injection (injection at the same time intervals) among the inverters cannot be reassured. Therefore, harmonic injection-based anti-islanding schemes will fail if the harmonic voltage component falls below a certain level. In this framework, a novel metric (i.e., the upgrade factor, UF) is introduced, indicating the supplementary power (of DERs) that can be installed in the same point of common coupling without compromising the effectiveness of the harmonic injection scheme. As this metric enables the evaluation of harmonic injection schemes prior to the future integration of DERs, it could be a substantial addendum into the relevant standards that evaluates the anti-islanding features of grid-tied DER-inverters. Finally, this paper proposes a technique (implemented in the software level), which maximizes UF and reassures the effectiveness of the harmonic injection schemes under the power variations of installed inverters. Extensive simulations and experimental tests have been conducted that verify the effectiveness of the proposed strategy under various penetration-levels and islanding-network conditions.