A method is proposed which avoids many limitations associated with traditional B-coefficient loss coefficient calculation. The proposed method, unlike the traditional B-coefficient method, is very fast and can handle line outages. The method utilizes network sensitivity factors which are established from DC load flow solutions, Line outage distribution factors (ODFs) are formulated using changes in network power generations to simulate the outaged line from the network. The method avoids the use of complicated reference frame transformations based upon Kron's tenser analysis. The necessity of data normalization used in least squares and the evaluation of the slope of /spl theta//sub j/ versus PG/sub n/ is not necessary with the proposed method. Using IEEE standard 14-bus and 30-bus systems, the method's results are compared against results obtained from an AC load flow program (LFED). The method's solution speed is compared to that of the LFED method, the base case database method and the conventional B-coefficient method based on A/sub jn/-factor. The proposed method is easy to implement and, when compared to other methods, has exhibited good accuracy and rapid execution times. The method is well suited to online dispatch applications.>
No takes yet. Share an insight, caveat, or question.
Chang et al. (1994) studied this question.