In this paper, design considerations for twelve-pulse diode rectifier systems operating under utility voltage unbalance and pre-existing harmonic voltage distortion are discussed. For a twelve-pulse diode rectifier system connected in parallel to feed a common DC link via an interphase transformer, it is shown that a small amount of impedance mismatch, utility voltage unbalance or pre-existing voltage distortion drastically affects the current sharing capability of the rectifier bridges. This, in turn, generates additional uncharacteristic and characteristic harmonics thereby increasing the THD. In order to mitigate these effects and ensure proper operation of diode rectifiers, specially designed line reactors termed harmonic blocking reactors (HBRs) are introduced. Analysis and design procedures for HBRs are discussed. Simulation results illustrate improved performance. Experimental results from a laboratory prototype system show close agreement with theory.