Polarization-Depolarization Current (PDC) analysis is a well known technique for condition monitoring of oil-paper insulation in power transformers. However, due to variation in insulation geometry, information obtained through analysis of PDC measured for one transformer cannot be used for predicting condition of another transformer even if the loading history of the two units are similar. Furthermore, parts of solid insulation closer to winding are exposed to much higher temperature than the parts away from it. Prolonged exposure to this temperature variation leads to nonuniform aging in cellulosic parts. It is reported that Modified Debye Model (MDM) is capable of modeling this non-uniform aging. In the present work it is shown that a parameter sensitive to insulation condition can be obtained from Transfer Function of MDM. Several laboratory samples having different physical dimensions has been constructed. PDC data recorded from these samples are used to obtain the performance parameter (which is less influenced by insulation geometry) and its relation to paper moisture content. The results obtained from the proposed method have been compared with that obtained using Frequency Domain Spectroscopy (FDS) based commercial instrument (IDAX 300) in the case of real-life power transformer.
No takes yet. Share an insight, caveat, or question.
Baral et al. (2014) studied this question.