Arc fault detection device (AFDD) is the latest protection device for low voltage circuits. It is used to detect arcing faults that cannot be detected by circuit breakers or residual current devices. Arcing faults are one of the main causes for electrical fires. Arc fault detection device is an active electronic device which operation is typically based on measurement of low and high frequency characteristics of the current passing through. Based on measured current characteristics and the knowledge of the arcing unique deviations in current, arc fault detection device detects possible arcing and disconnects the protected circuit. Arc fault detection device as an active electronic device is a potential source and victim of electromagnetic interference. Electromagnetic compatibility requirements are especially very demanding in military applications where low emission levels and high immunity levels are required. This article presents test results from electromagnetic compatibility testing of five different commercial arc fault detection devices against military standard requirements and analyses the suitability of the arc fault detection devices in military electromagnetic environment.