A new control strategy is introduced for operating anaerobic digestion processes efficiently at high load. The control system includes a cascade controller embedded into a rule-based supervisory system based on extremum-seeking control. The control system measures pH and biogas production rate and varies the organic load by manipulating the influent flow. Good control performances were achieved during the start-up and steady-state running operations and during rejection of disturbances. The control system can run the process under a high load condition and efficiently reject disturbances without explicit measurement of the influent characteristics.
No takes yet. Share an insight, caveat, or question.
Liu et al. (2004) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: