This paper presents analysis and control of a hybrid filter that can suppress neutral harmonic currents in three-phase four-wire systems not only with harmonic voltage-source loads but also with harmonic current-source loads. The filter voltampere rating is significantly reduced compared to the conventional neutral-current-suppressing methods. The rectifier part of the neutral harmonic suppressor has been removed by controlling the dc capacitor voltage. The experimental results on a 50-kVA prototype validate the proposed control approach.
No takes yet. Share an insight, caveat, or question.
Choi et al. (2007) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: