This paper uses the eigenvalue analysis approach to observe the impact of load models on an unstable low frequency oscillation damping, which recently occurred in the Taiwan power system. In order to enhance oscillation damping, the effect of load models on power system stabilizers is also investigated. Three kinds of the derived load models (a dynamic model, a composite model, and an exponential model) based on the component approach with the measured characteristics of power system loads are used in this paper. Time simulation results are extensively used to verify the eigenvalue analysis results with and without power system stabilizers. One set of field test data obtained from the Taiwan power nuclear plant with power system stabilizers is used to determine which load model provides a more accurate result in enhancement of oscillation damping. Depending on the results, the effect of load models on electromechanical oscillation damping with and without power system stabilizers is verified.
No takes yet. Share an insight, caveat, or question.
Wen-Shiow Kao (2001) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: