Answers are grounded in this paper and cite their sources.
The voltage stability is an essential security concern when a system is operating in peak load hours or subjected to an N-1 contingency. Among various voltage stability indices, Local Thevenin Index (LTI) has been a popular one, but mostly applied to the measurement-based framework. The reason is that it requires significant computing effort if applied to model-based approach, even though the model-based LTI calculation can provide more accurate results. In this paper, a new model-based LTI calculation is proposed using graph-computing-based power flow calculation, which is fast enough to fully utilize the advantage of model-based LTI. Then, when the voltage stability index of one or multiple buses exceeds the security limit, a demand response scheme is activated to increase the voltage security margin at the lowest cost. The simulation study of a thousand-level-bus system verifies the computation accuracy and efficiency of the proposed model-based LTI. It also demonstrates that the demand response action can enhance the system security effectively. Thus, the proposed work has advantages if applied to a large-scale Energy Management System (EMS).
No takes yet. Share an insight, caveat, or question.
Shi et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: