Power quality and voltage control are among the most important aspects of the grid-connected power converter operation under faults. Nonsinusoidal current may be injected during unbalanced voltage sag, and active or/and reactive power may include double frequency content. This paper introduces a novel control strategy to mitigate the double grid frequency oscillations in the active power and dc-link voltage of the two-stage three-phase grid-connected photovoltaic (PV) inverters during unbalanced faults. With the proposed control method, PV inverter injects sinusoidal currents under unbalanced grid faults. In addition, an efficient and easy-to-implement current limitation method is introduced, which can effectively limit the injected currents to the rated value during faults. In this case, the fault-ride-through operation is ensured, and it will not trigger the overcurrent protection. A non-maximum power point tracking (non-MPPT) operation mode is proposed for the dc-dc converter. The mode is enabled under severe faults when the converter cannot handle the maximum PV power. Finally, experimental validation is provided by implementing a method in an experimental setup, including a 2 kW PV inverter.