This letter presents a side-hole fiber-based extrinsic Fabry–PÉrot interferometric (EFPI) sensor whose cavity was filled with sulfur hexafluoride (SF₆) forin situpower transformer partial discharge detection. The Fabry–PÉrot cavity was formed by a polished thin diaphragm and a cleaved side-hole fiber that were thermally fused onto a fused silica ferrule. The cavity was first vacuumed and then inflated with 300-kPa SF₆through the fiber side holes to increase its resistance to electric stress. Experimental results show that the sensor filled with SF₆was able to withstand electric stress of at least 10 kV/mm (ac root-mean-square value) in transformer oil, three times larger than that of a traditional air-filled EFPI sensor.