This paper deals with the combined least mean square–least mean fourth (LMS–LMF)-based control algorithm for distribution static compensator (DSTATCOM) in three-phase distribution system to alleviate the power quality problems caused by solid-state equipments and devices. The combined LMS–LMF-based algorithm is simulated using Sim Power System (SPS) toolbox in MATLAB for obtaining the corresponding active and reactive weights and supply reference currents. The proposed control algorithm has advantages of both LMF- and LMS-based control algorithms, which helps in fast and accurate response with a robust design. Depending on the value of error signal obtained in any of the phases either of LMS- or LMF-based control is used to minimize the error. The developed combined LMS–LMF-based algorithm is implemented on the prototype of the proposed system and responses obtained are found satisfactory with harmonic spectra of the supply currents meeting the power quality standards.