This paper presents a two-timescale multi-objective coordinated volt/var optimization system for active distribution networks with renewable energy resources (RESs). In the hourly timescale, power loss and the number of control actions of on-load tap changers and (switchable) shunt capacitors for 24 h are minimized by coordinating on-load tap changers, (switchable) shunt capacitors, and reactive power outputs of RESs. A three-step method consisting of global search, user preference, and local search is adopted to solve the corresponding multi-objective mixed-integer nonlinear optimization problem. A rolling volt/var optimization is executed every 6 h, considering the day-ahead RES forecast errors. In the 15-min timescale, the RES reactive powers are optimized with RES uncertainties explicitly taken into consideration to minimize the pilot-bus voltage deviation under all representative scenarios. The pilot buses are those buses whose voltage magnitudes capture the network voltage profile. In this paper, a linear method is applied to quickly identify a set of pilot buses, and the impact of the identified pilot bus on the entire network voltage profile is evaluated. The IEEE 33-bus distribution network is used to evaluate the proposed two-timescale volt/var optimization formulations and methods with promising results.