An identification technique is described, based on a developed adaptive fuzzy logic network, that enables the recognition of partial discharges (PD) generated by different defects in heat-shrinkable joints and terminations of XLPE insulated power distribution cables. It is shown that different sources of PD can be identified on the basis of fuzzy rules applied to a selection of parameters derived from PD-pulse phase and amplitude distributions. A comparison with other PD pattern recognition techniques based on traditional neural networks is presented and discussed.
No takes yet. Share an insight, caveat, or question.
Mazzetti et al. (2006) studied this question.
Synapse has enriched one closely related paper. Consider it for comparative context: