The dielectric recovery in high-voltage circuit breakers after interruption of high-current amplitudes was investigated experimentally in a test device. Various current amplitudes were tested, which cover a typical range of practical interest. Simulations with computational fluid dynamics together with electric field simulations allowed one to deduce the physical parameters in the region where the breakdown was decided. A leader inception model using these parameters explains under which condition leader inception occurs; causing breakdown of the gap. Based on this model scaling laws for leader inception are given.
No takes yet. Share an insight, caveat, or question.
Seeger et al. (2012) studied this question.