A sustained current conduction in the breaking chamber after a current interruption has been observed. This current, which we named 'Post-recovery (PR) current', is in phase with the applied voltage and its value ranges from several milliamps up to several amps. The present study shows that the probable origin of the PR current is an ionic conduction of SF 6 between the contacts. The estimated temperature of the conducting gas is about approximately 2000 K. The evolution of the temperature is in good accordance with a computational model based on the resolution of two-dimensional Navier-Stokes equations.
No takes yet. Share an insight, caveat, or question.
Maftoul et al. (1995) studied this question.