This paper proposes a co-ordinated four-loop switching controller (SC) for the doubly fed induction generator (DFIG) to improve the transient stability of wind power penetrated power systems. A short-term resilience index is introduced, and it reflects the dynamics of both system frequency and load bus voltage. A four-loop SC is driven by the four outputs of a DFIG, namely, the rotor speed deviation, the reactive power output of stator winding, the reactive power transferred through grid-side converter, and the DC-link voltage, respectively. Referring to a state-dependent switching strategy, the four-loop SC switches between a logic-based bang-bang constant funnel controller (LBCFC) and a vector control theory-based conventional controller (CC) in each control loop. The LBCFC is robust to system nonlinearities, uncertainties, and external disturbances. The control signal of the LBCFC is bang-bang with the upper and lower limits of control variables. Simulation studies are undertaken in a modified IEEE 16-generator 68-bus power system, in which four DFIG-based wind farms are penetrated to provide 9.94% power supply. The performance of the four-loop SC is evaluated in aspects of the integral control of the DFIG and the resilience enhancement of the multimachine power system, respectively.