Moving target defense (MTD) is a defense strategy to detect stealthy false data injection (FDI) attacks against the power system state estimation using distributed flexible AC transmission system (D-FACTS) devices. However, existing studies neglect to address a fundamental yet critical issue, i.e., the D-FACTS placement, by assuming that all lines are equipped with D-FACTS devices. To tackle this problem, we first derive analytical necessary conditions and requirements on the D-FACTS placement for a complete MTD. Further, we propose sufficient conditions using a graph theory-based topology analysis to ensure that the MTD under the proposed D-FACTS placement has the maximum rank of its composite matrix, which is indicative of the MTD effectiveness. Based on the analytical conditions, we design D-FACTS placement algorithms by using the minimum number of D-FACTS devices to achieve the maximum MTD effectiveness. A novel MTD-based ACOPF model, in which the reactance of D-FACTS lines is introduced as decision variables, is proposed to find a trade-off between the system loss and the MTD effectiveness. Numerical results on 6-bus, IEEE 14-bus, and IEEE 118-bus systems show the efficacy of MTDs using the proposed D-FACTS placement algorithms in maximizing the composite matrix rank and detecting FDI attacks.
No takes yet. Share an insight, caveat, or question.
Liu et al. (2020) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: