Synchronization with the power system is an essential part of control of grid-connected converters. This paper proposes a grid-voltage sensorless synchronization and control scheme for a converter equipped with an LCL filter, measuring only the converter currents and the dc voltage. A discrete-time pole-placement design method is used to formulate an adaptive full-order observer for the estimation of the frequency, angle, and magnitude of the grid voltage. The proposed discrete-time design method enables straightforward implementation and suits low sampling rates better than its continuous-time counterpart. The analytically derived design is experimentally validated, and the results demonstrate rapid convergence of the estimated quantities. Moreover, the experimental tests show that grid-voltage sensorless operation is possible under balanced and unbalanced grid disturbances and distorted grid conditions.