Fluid flow and heat transfer over a 4-row. elliptic, finned-tube heat exchanger having an axis ratio of 2.83:1 are studied experimentally and numerically. Three types of finned-tube configurations have been investigated under dry and wet conditions for different values of inlet frontal velocity ranging from 2 to 7 m/s: two elliptic finned tubes with staggered and in-line arrangements and one circular finned tube with staggered arrangement. The experimental results indicate that the average heat transfer coefficient of an elliptic finned lube is 35–50% of the corresponding circular finned tube having the same tube perimeter, while the pressure drop for an elliptic finned-tube bank is only 25–30% of the circular finned-tube bank configuration. Three-dimensional numerical results of a laminar model for dry coils are also presented and are compared with the experimental data.
No takes yet. Share an insight, caveat, or question.
Jang et al. (1998) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: