In this paper, the circulating current caused by dead time is discussed for a grid‐connected inverter parallel system (GIPS) with common/isolated DC link. When the dead times for parallel units are different, the instantaneous output pulse width modulation (PWM) voltages cannot be synchronous, generating a circulating current. According to the operating modes, the trend of variation of the circulating current is revealed in one sampling period. In order to eliminate the circulating current caused by the dead time, dead‐time elimination sinusoidal pulse‐width modulation (SPWM) is applied to GIPS. The dead‐time elimination PWM generator is integrated into the field‐programmable gate array (FPGA). Experimental results are presented to demonstrate the validity and features of the proposed dead‐time elimination SPWM.