Modern fault-resilient microgrids (MGs) require the operation of healthy phases during unbalanced short-circuits to improve the system reliability. This study proposes a differential power based selective phase tripping scheme for MGs consisting of synchronous and inverter-interfaced distributed generators (DGs). First, the differential power is computed using the line-end superimposed voltage and current signals. Subsequently, to make the scheme threshold-free, a power coefficient index is derived and used for identifying faulted phases in an MG. The protection scheme is tested on a standard MG operating in either grid-connected or islanding mode, which is simulated using PSCAD/EMTDC. The efficacy of the scheme is also assessed on the OPAL-RT manufactured real-time digital simulation (RTDS) platform. Further, the performance of the proposed protection scheme is compared with a few existing methods. The results show that the selective tripping of faulted phases in MGs can be achieved quickly and securely using the proposed scheme.
No takes yet. Share an insight, caveat, or question.
Anudeep et al. (2022) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: