Partial discharge (PD) is one of the sources of insulation failures in Power transformers. Knowledge of the PD source locations are important for transformer maintenance and repair. Due to the complex structure of the transformer, it is very difficult to locate the PD accurately in transformer winding. Correlation methods are applied to locate the PD source across the winding. The PD across parts of the winding are simulated by applying voltage pulse across the sections. The winding response for a reference PD impulse across transformer sections are taken as base for correlation and correlated with winding response of PD impulse across any section with different PD pulse widths. In this paper the limitation of time domain correlation method in locating PD in transformer windings is found out. To overcome the limitation of time domain correlation method, frequency domain correlation with Gram Schmidt orthogonalization is proposed. Simulation and experiments are performed on layer, continuous disc and interleaved windings to prove the feasibility of the proposed method.