Data recorded by intelligent electronic devices such as protective relays contain a wealth of valuable information that can be used beyond post-mortem analysis of fault events. The objective of this paper is to propose algorithms to estimate zero-sequence line impedance and fault resistance using protective relay data collected during short-circuit fault events. Protective relaying data may be available from one or both ends of the line. For the latter, they may be collected at different sampling rates with dissimilar fault time instants. Furthermore, they may be unsynchronized. This paper presents approaches which uses measurement data from one and both ends of the line. The efficacy of the proposed algorithms presented in this paper are demonstrated using a test case as well as field data. The error percentage of the zero-sequence line impedance magnitude estimated using the data from both ends of a two-terminal line was under 3% for all the test cases. The error percentage in estimating the fault resistance was less than 1% in the test cases presented.
No takes yet. Share an insight, caveat, or question.
Das et al. (2017) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: