When a fault occurs on a power system, one or more phases will experience DC offset. This DC component, which will decay dependent on the L/R time constant of the system, can produce saturation in the current transformers, as well as the input current transformers of the protective relays sensing the fault. In addition, when the fault current is interrupted, the resulting DC tail can maintain the current above the relay's pickup setting for a time dependent on the current transformer secondary circuit L/R time constant. This paper discusses this phenomenon and how it can affect the operation of two types of current-operated relays.
No takes yet. Share an insight, caveat, or question.
N.T. Stringer (1998) studied this question.
Synapse has enriched 5 related papers. Consider them for comparative context: